Permit: T04CM02971

Parcel: 137055220


Addresses:

1221 W IRVINGTON RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T04CM02971

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/28/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
12/21/2005 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
OK - RECEIVED BACKFLOW CERTS FOR CARBONATORS - OK
1. SUPPORT DRAIN PIPING AT 2 COMP SINK
2. COMPLETE INSTALLATION ON HB VAC BREAKERS
ROOF USE LLC WILL SEAL AND WARRANTY ROOF PENETRATIONS OLD GAS PIPING HAS BEEN REMOVED
12/16/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* CALL IN ANY UNAPPROVED INSPECTIONS SO THEY CAN BE SIGNED ??
3075 PROGRESS
3035 INTERMEDIATE
IDENTIFY ANSEL VALVE LOCATIONS
INSTALL RESTRAINT ON MOVABLE GAS APPLIANCE
INSTALL ROOF FLASHINGS AT GAS & VENT PENETRATIONS
PROVIDE UV PROTECTION ON EXPOSED ABS
EITHER REMOVE OLD GAS SYSTEM AS REQUIRED PER PLAN OR RED LINE PRINT FOR AS BUILT AND PROPERLY SUPPORT OLD GAS PIPING AND REMOVE STRAIN ON PIPING
PROVIDE APPROVED LISTED CLEANOUT PLUGS DESIGNED TO RECEIVE A SCREW. DRILLING ABS IS PROHIBITED
SUPPORT WATER SUPPLY TO PROOF BOX OVERHEAD
DRAINAGE FITTINGS REQUIRED ON SINK DRAINS A SANTEE ON ITS BACK IS NOT THE CORRECT DRAINAGE FITTING
PROVIDE MIN ACR GAP REQUIREMENTS ( 2X EFFECTRIVE OPENING) ON INDIRECT DRAINS.
INSTALL BACKFLOW PROTECTION FOR ICE MAKER & POTABLE WATER AT ? 00 A FOUNTAIN OR PROVIDE PROOF OF AIR GAP.
PROVIDE CERTIFICATION PAPER WORK ON RP FOR CARBONATOR
PROVIDE PERM CAPS ON ALL DEMOED FIXTURES
RED LINE PRINT FOR FIXTURES NOT DEMOED PER PRINT