Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04CM02971

Parcel: 137055220


Addresses:

1221 W IRVINGTON RD


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T04CM02971

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
12/28/2005 PLUMBING - GAS PRESSURE TEST Approved
12/15/2005 PLUMBING - GAS PRESSURE TEST Partial Approval 60 PSI TEST ON ROOF TOP PIPING OK
OK FOR GAS SWITCH OVER ANSE VALVE TEST
REQUIRE SOAP TEST AT FINAL
PROVIDE PIPING SUPPORTS AND FLASHING AT PENETRATION
12/06/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*3 SYSTEMS TESTED THRU ROOF OK
1 1/4 TO TORTILLA OVEN 15 PSI
1.2 TO FRYER 12 PSI
1" AND 1 1/4" KITCHEN 12 PSI
10/14/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :* GAS IN WALLS TO OVERHEAD AT ANSUL VALVE OK TO COVER
ABS IN WALLS TO OVERHEAD OK
COPPER IN WALLS OK
OK TO INSULATE.