Permit: T04CM02971

Parcel: 137055220


Addresses:

1221 W IRVINGTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T04CM02971

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/16/2005 ELECTRIC - ABOVE CEILING Approved
12/07/2005 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
12/06/2005 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*MC CABLE MUST BE SUPPORTED WITHIN 12" AT TERMINATIONS & AT 6' INTERVALS.
COMPLETE J-BOX MAKE UP
J-BOXES IN WOOD SOFFITS NOT ACCESSIBLE
11/21/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*COMPLETE MAKEUP IN J-BOXES, PANEL HOME RUNS, MC OR FLEX MUST BE TIED UP ?? TO LAY ON GRID
11/18/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*1) BEND OUT ALL FOUR TABS AT LIGHT FIXTURE CORNERS & PRESS AGAINST GRID.
2) SUPPORT J + BOXES FROM STRUCTURE, NOT GRID.
3) INSTALL BUSHINGS IN PANELS