Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM02971
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/16/2005 | ELECTRIC - ABOVE CEILING | Approved | ||
12/07/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
12/06/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*MC CABLE MUST BE SUPPORTED WITHIN 12" AT TERMINATIONS & AT 6' INTERVALS. COMPLETE J-BOX MAKE UP J-BOXES IN WOOD SOFFITS NOT ACCESSIBLE |
|
11/21/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*COMPLETE MAKEUP IN J-BOXES, PANEL HOME RUNS, MC OR FLEX MUST BE TIED UP ?? TO LAY ON GRID | |