Inspection Status: Approved
Inspection History: STUCCO MESH
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/12/2004 | STUCCO MESH | Approved | IVRS - Inspection :* | |
| 11/01/2004 | STUCCO MESH | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) BACK PATIO LIGHT NOT GROUNDED 2) REPAIR BURNED LATH AT POOL HOSE BIB 3) USE APPROVED NAIL PROTECTION AT SOFFIT WATER LINES 4) SEAL M/PENETRATIONS FROM FIRST TO SECOND FLOOR AND INTO ATTIC SPACE 5) NAIL PROTECT ALL PLUMBING WITHIN 1 1/2" FROM EDGE OF STUD 6) FIXTURE BOXES NOT GROUNDED 7) HOOD DUCT DISCONNECTED 8) RAT RUNS CUT 9) HAVE TRUSS REPAIR APPROVED BY CITY OF TUCSON 10) LOOSE A.B.'S 11) COMPLY WITH DETIAL 50 AD3 12) COMPLY WITH 4SD4 SHEAR PANELS 13) FIRE BLOCK POP OUT 2ND FLOOR 14) NO TEST ON DWV'S UPSTAIRS 15) SEAL PENETRATIONS AT MAIN WATER, AT NORTH EAST WALL 16) STOPPED INSPECTION |
|
| 10/29/2004 | STUCCO MESH | Denied | IVRS - Inspection : See detailed listing on site.| 999* |