Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 02/11/2005 | BUILDING - FINAL | Partial Approval | 1) NEED VERIFICATION OF 01045 APPROVAL 2) MOVE GAS PIPING AWAY FROM ROOF UNIT FOR ACCESS TO ELECTRIC PANEL BOX 3) TRAP AND VENT ROOF CONDENSATE 4) CONDENSATE LINE HAS NEGATIVE PITCH 5) INSTALL POST TENSION TAG ON H20 SERVICE PIPING EXTERIOR |