Permit: T04CM02950

Parcel: 108163630

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/20/2004 FRAMING Approved IVRS - Inspection :*
12/15/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 3P #4 SHEAR NOT PER PLAN
2) PROVIDE TERRITORIAL SHEAR PLAN
3) BR 2 SHEAR WALL 1 REQUIRED STUDS AT 16" ON CENTER PER 1/D3 AND BR 3
4) BLOCK BETWEEN LADDER BACK PER 1/D3
5) LESS THAN 2" CLEARANCE AT F/P 'B' VENT
6) RANGE BOX MISSING
7) RED HEAD A/B LOOSE
8) NO GAS BOND
9) SUPPORT VENT 90 ELBOW AT ROOF PENETRATION
10) SEAL MASTER BATH FROM OUTSIDE
11) FIRE STOP REQUIRES 2 LAYERS OF OSB 1/2" OR 1 3/4"
12/13/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAILS MISSING AT ? TRUSS HANGER ABOVE WATER HEATER PLATFORM
2) FIRE STOP NEEDED SINGLE GARAGE DOOR WEST END
3) REPLACE FIRE BLOCK NORTH GARAGE WALL
4) SHIM HEADER REAR PORCH WINDOW
5) SEAL OUTLET BOX ABOVE SERVICE PANEL
6) GROUND ALL METAL BOXES
7) NAIL PROTECT ROMEX BELOW DINING ROOM WINDOW
8) NAIL PROTECT ROMEX THROUGHOUT HOME UNDER 1 1/4"
9) NAIL PROTECT PEX AT WATER SOFTNER
10) PROVIDE TRUSS CALC'S
11) DMV AND WATER TESTS OK