Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/15/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :*/ 1) OK FINAL |
| 09/14/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ 1) INSPECTOR NOT TO ACCESS LIVE TRANSFORMER. PLEASE HAVE ELECTRICIANS OPEN FOR INSPECTION |
| 09/13/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/1)FURNITURE CONNECTION BROKEN-WE HAVE EXPOSED CONDUCTORS 2)PROTECT NEW VDV CABLES FROM SHARP METAL EDGES 3)SECURE TRANSFURNIER? TO FLOOR 4)CAN NOT STACK LUGS? |
| 09/01/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 08/19/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/PHASE ONE OK, FINAL PHASE ONE. FINISHING POWER POLES |