Permit: T04CM02932

Parcel: 13104398A


Addresses:

4701 E 29TH ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
03/22/2005 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
03/21/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :* WATER TEST WASTE & VENT THRU ROOF OK. 1) FLOOR CLEANOUTS WILL REQUIRE ?? PATTERN CLEANOUTS COVERS. 2) NEED TO SEE PIPE WRAPS PRIOR TO CONCRETE POUR BACK. 3) COFFE, SODA, ICE MACHINE MAY REQUIRE BACKFLOW PROTECTION FOR FINAL. SEE NOTE # 5 P-1
03/16/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :* 1) FLOOR SINK REQUIRES APPROVED TRANSITION COUPLING FOR ABS TO CAST IRON. ( NO HUB COUPLING IS NOT) 2) PROVIDE TRANSITION COUPLING AT 4" BUILDING DRAIN CONNECTOR TO NEW ABS. 3) P-4 FIXTURE MAY REQUIRE 1 1/2 DRAIN ARM( 2X2X1/1/2 SANTEE) IF TAILPIECE OF FIXTURE IS 1 1/4"
03/14/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :* 1) PIPE TO PITCH AT 1/4" PER FOOT. 2) VENT DOWNSTREAM OF TRAP. 3) VENT TO RISE VERTICALLY. 4) USE APPROVED STRAP. 5) PROVIDE FOR INSULATION 6) CLEAN OUT YARDWATER TRENCH AND RECALL FOR INSPECTION.