Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/29/2004 |
PLUMBING - INTERMEDIATE |
|
Approved |
|
| 08/16/2004 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ 1) TEST OK ON WASTE VENTS AND WATER 2) PLEASE PROVIDE LETTER FROM ARCHITECT ON SLEEVE FOR PIPE PENETRATIONS FIRE CAULK HAS BEEN INSTALLED AND INSULATION HAS BEEN INSTALLED |
| 08/12/2004 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) PLEASE REPAIR LEAK ON 3 X 2 WYE 2) SEE SPEC FOR FIRE CAULK AND INSULATION 3) ALSO SPECS CALL FOR CARRIERS AT LAV 3) PLEASE PROVIDE DIRECTION FROM ANCHOR ON PIPE PENETRAITON TRHU FLOOR |