Permit: T04CM02923


Addresses:

4209 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T04CM02923

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/30/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/18/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* 1) 400AMP DISCONNECT FOR COMPRESSOR RCACK OK 2) 400AMP COMPRESSOR UNIT OK
01/12/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* 1) CONDUCTORS & SWITCH FOR REFER. COMPRESSOR PLATFORM
01/10/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*1) TERMINATIONS & CABLE SIZES PNLS CP, PA & B, PC & PM
12/03/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) BOTTOM 1/2 DEMISSING WALL-SOUTH
12/02/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) CABLES CANNOT BE SUPPORTED BY OTHER CABLE RUNS
2) MC CABLES MUST BE STAPLED WITHIN 8" OF BOX
3) MC CABLES OUT OF WALL
4) MC CABLES OUT OF CEILING (FRAME AREA)
5) MC CABLES IN WALL FRAMING STUDS RUN THRU HOLES WITHIN 1 1/4" FROM FACE OF STUD REQUIRE NAIL PLATE
6) HOW WILL MC TERMINATE ON SURFACE ? FLOOR FIXTURES ?