Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM02923
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/30/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/18/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 400AMP DISCONNECT FOR COMPRESSOR RCACK OK 2) 400AMP COMPRESSOR UNIT OK | |
01/12/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CONDUCTORS & SWITCH FOR REFER. COMPRESSOR PLATFORM | |
01/10/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*1) TERMINATIONS & CABLE SIZES PNLS CP, PA & B, PC & PM | |
12/03/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) BOTTOM 1/2 DEMISSING WALL-SOUTH | |
12/02/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) CABLES CANNOT BE SUPPORTED BY OTHER CABLE RUNS 2) MC CABLES MUST BE STAPLED WITHIN 8" OF BOX 3) MC CABLES OUT OF WALL 4) MC CABLES OUT OF CEILING (FRAME AREA) 5) MC CABLES IN WALL FRAMING STUDS RUN THRU HOLES WITHIN 1 1/4" FROM FACE OF STUD REQUIRE NAIL PLATE 6) HOW WILL MC TERMINATE ON SURFACE ? FLOOR FIXTURES ? |