Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
09/15/2004 ELECTRIC - RECONNECT Approved IVRS - Inspection :* CLEAR RECON
09/03/2004 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) YOU NEED TO GRD RODS
06/28/2004 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) NO GROUNDING, OK WATER BOND AT EITHER, SERVICE DISCONNECT, YOU NEED TWO GRD RODS 2) REPLACES FUSES 3) CLEAN UP CONNECTIONS AND WIRING 4) PLUG HOLES IN BOTH BOXES 5) REMOVE CONDUIT AND WIRE TO CARPORT 6) YOU NEED A NEW SUB/PANEL, OLD ONE, HAS NO SPACE FOR FURANCE CIRCUIT IT WAS WIRED INCORRECTLY 7) ALL OUTLETS IWHT GRD TYPE RECEPTACLE, TO BE REPLACED WITH A GFCI, OR UN GROUND TYPE 8) CABINET CANNOT BE IN FRONT OF SUB/PANEL 9) YOU NEED STICK UP TYPE SMOKE DETECTORS IN ALL BEDROOMS AND ONE AT ENTRY TO HALLWAY 10) LOW VOLTAGE WIRING AT SOLAR ARRAY IS ALL DAMGED EXPOSED TO WEATHER 11) REAR COOLER NEED A WEATHER TIGHT BOX, A FUSED ARIZ BOX WOULD BE BETTER 12) I LEFT THE COVER OFF THE SUB-PANEL SO YOU COULD SEE WHAT WAS DONE TO THE WIRING