Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 12/30/2004 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection :*APPROVED. |
| 12/29/2004 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |