Inspection Status: Approved
Inspection History: STEM WALL/RETAINING WALL
Permit Number - T04CM02898
Inspection Description - STEM WALL/RETAINING WALL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/04/2004 | STEM WALL/RETAINING WALL | Approved | IVRS - Inspection :*/ 1) JAMB BARS AS "BUNDLED" OK PER E.O.R. 9/30/04 | |
09/30/2004 | STEM WALL/RETAINING WALL | Partial Approval | 1) CHAIR EDGE AT OPENINGS FOR PROPER CLEARANCE 2) ADJACENT #5 JAMB BARS REQUIRE 1" CLEAR PER ACI OR RFI FROM ENGINEER SAYING BUNDLED IS OK ( 1/2" SEPERATION ) 3) CHAIR WIDE JAMBS SO FINISHERS CAN'T CRUSH STIR-UPS 4) OK TO PLACE WHEN E.O.R., CONFIRMS |