Permit: T04CM02898

Parcel: 135074590


Addresses:

8100 E RESEARCH CT


Inspection Status: Approved

Inspection History: STEM WALL/RETAINING WALL

Permit Number - T04CM02898

Inspection Description - STEM WALL/RETAINING WALL

Inspection Status - Approved

Date Description Inspector Results Comments
10/04/2004 STEM WALL/RETAINING WALL Approved IVRS - Inspection :*/ 1) JAMB BARS AS "BUNDLED" OK PER E.O.R. 9/30/04
09/30/2004 STEM WALL/RETAINING WALL Partial Approval 1) CHAIR EDGE AT OPENINGS FOR PROPER CLEARANCE 2) ADJACENT #5 JAMB BARS REQUIRE 1" CLEAR PER ACI OR RFI FROM ENGINEER SAYING BUNDLED IS OK ( 1/2" SEPERATION ) 3) CHAIR WIDE JAMBS SO FINISHERS CAN'T CRUSH STIR-UPS 4) OK TO PLACE WHEN E.O.R., CONFIRMS