Inspection Status: Approved
Inspection History: STEM WALL/RETAINING WALL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/04/2004 |
STEM WALL/RETAINING WALL |
|
Approved |
IVRS - Inspection :*/ 1) JAMB BARS AS "BUNDLED" OK PER E.O.R. 9/30/04 |
| 09/30/2004 |
STEM WALL/RETAINING WALL |
|