Permit: T04CM02889

Parcel: 130140260


Addresses:

4082 E 22ND ST

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
07/08/2004 FIRE SPKLR - FINAL Approved 1) OK C OF O
07/02/2004 FIRE SPKLR - FINAL Denied 1. One fire sprinkler needs to be added in the corner adjecent to the main riser.
2. Remove old sprinkler drops to walk-in coolers that have been removed.
3. Provide current fire sprinkler maintenance/inspection report.
07/01/2004 FIRE SPKLR - FINAL Denied Business locked. Unable to inspect.