Permit: T04CM02881

Parcel: 110035640

Inspection Status: Approved

Inspection History: PLUMBING - ROOF DRAINS

Date Description Inspector Results Comments
10/18/2007 PLUMBING - ROOF DRAINS Approved IVRS - Inspection :*
1. 6" RWL & 6" OVERFLOW FROM ROOF DRAIN TO EXIT
AT BLDG OK
2. WATER TEST OK
3. CONTRACTOR TO INSTALL SWAY BRACING ON OVERHEAD AS REQUIRED
10/15/2007 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
- TEST REQUIRED, CORRECTIONS WERE MADE AT CHANGE OF DIRECTION
- PROVIDE LADDER TO CHECK SPACE
- PROVIDE PLAN
07/09/2007 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
RWL #11 OK
DECK DRAINS NEED APPROVED PLAN REVISIONS
MAIN RWL BETWEEN COLS 2-5 NOT PER PLAN

706.1 -- HORIZ. BY HORIZ CHANGES OF DIRECTION SHALL BE MADE BY THE APPROPRIATE USE OF APPROVED FITTINGS AND SHALL BE OF THE ANGLES PRESENTED BY 1/16 OR 1/8 BENDS OR SWEEPS OF EQUIVALENT RADIUS.
SEE ILLUSTRATED TRAINING MANUAL FIG. 7-13
07/05/2007 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
3" RWL ON WEST SIDE UNDER TEST PROVIDE PLANS