Permit: T04CM02875

Parcel: 110034820

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
11/03/2008 PLUMBING - ROUGH, SOIL Approved
10/03/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
2" DRAIN INSTALLED PER REDLINE FROM ELEVATOR LOCATION TO 4" WASTE 10' TO THE WEST. CONDENSATE MAY TERMINATE INTO AN APPROVED RECEPTOR - OK TO COVER SUBJECT TO APPROVED PLAN. TRAP NOT INSTALLED.
09/26/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
03/01/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
4" SCH 40 PVC DRAIN STUBBED INTO BUILDING
02/27/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SDR NOT APPROVED FOR USE WITHIN THE BUILDING.
2. USE SCH 40 IF PER PLAN. TEST TO 10'
3. CORRECT SLOPE ON 2 WAY CO
4. TERMINATE TRACER WIRE AT CO
5. WATER LINE PVC FROM METER LOCATION TO BUILDING OK
6. PVC NOT APPROVED FOR USE UNDER BUILDING
7. NEED TO SEE CONNECTIONS AT BUILDING AND AT RP AND METER.