Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM02850
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/14/2004 | FRAMING | Approved | IVRS - Inspection :* | |
10/13/2004 | FRAMING | Partial Approval | IVRS - Inspection :*/ 1) OK TO INSULATE | |
10/12/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NAIL SECOND FLOOR SILL PLATES AT 16" ON CENTER 2) PROVIDE 1" CLEARANCE ON W/H "B" VENT AND FIREBLOCK |
|
10/11/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PROVIDE 1/4" PER FOOT AT DRAINS 2) SEAL LATH FROM INSIDE 3) NAIL PROTECT CONDENSATE LINES 4) FLASHING NOT INSTALLED AT COPPER LINES FOR CONDENSOR 5) NO ELECTRIC WIRE WITHIN A 6' RADIUS OF ATTIC OPENING 6) STOPPED INSPECTION |