Permit: T04CM02800

Parcel: 138241840

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
11/23/2004 BUILDING - FINAL Approved IVRS - Inspection :*
11/19/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) WATER HEATER T & P LINE MUST EXHAUST 6" ABOVE GRADE
2) WATER HEATER VENT JOINTS NOT TAPED
3) ALL GARAGE ELECTRIC OUTLETS MUST BE GFCI PROTECTED
4) RETURN AIR CHASE REQUIRES 300 SQUARE INCH OPENINGS ONLY 130 SQUARE INCH EXISTS