Permit: T04CM02796

Parcel: 10510079B


Addresses:

427 E LIMBERLOST DR

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
12/02/2005 MECHANICAL - HOODS Approved
11/14/2005 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
08/07/2005 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) AS PER 8/4/05 PROCEED AS /FIRE WRAP IF CERTAIN THAT REVISED METHOD WILL BE ACCEPTABLE/AGREEABLE TO ENGINEER/OWNER ETC...
08/05/2005 MECHANICAL - HOODS Partial Approval COMM. KITCHEN HOOD
HOOD ON JOB IS 12 FT. X 4 FT.
16 GA. BLACK IRON EX. DUCT IS BASE, 16" X 17" W/TRANSITION TO 17" SQ. APPROVED DRAWING FROM ENGINEER MUST SHOW THESE DIMENSIONS AS CORRECT.
OK TO FIRE WRAP EXHAUST DUCT, AS PER DISCUSSION
07/26/2005 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
HOOD IN KITCHEN W/EXHAUST DUCT ATTACHED IS NOT WHAT APPROVED PLAN IS SHOWING - NEED TO COORDINATE AS NECESSARY