Permit: T04CM02796

Parcel: 10510079B


Addresses:

427 E LIMBERLOST DR

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
06/23/2005 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE
06/17/2005 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999* PROVIDE CONDENSATE DRAIN TO AN APPROVED LOCATION VENTS FROM WATER HEATER CANNOT RUN FLAT. 1-60 DEGREE OFFSET ALLOWED. PENETRATION THRU ROOF MUST BE 8' AWAY FROM 2ND STORY WALL OR EXTEND TO 2' ABOVE UPP3ER ROOF. OK TO SHEET ROCK JOISTS WITH 5/8 FIRE RATED SHEET ROCK IF 1" CLEARANCE CANNOT BE MAINTAINED. 2ND FLOOR INSTALL REFER LINES. REMOVE SCREEN FROM DRYER VENT T -TOP. NO ABOVE CEILING ON THIS JOB