Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2005 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE | |
| 06/17/2005 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE CONDENSATE DRAIN TO AN APPROVED LOCATION VENTS FROM WATER HEATER CANNOT RUN FLAT. 1-60 DEGREE OFFSET ALLOWED. PENETRATION THRU ROOF MUST BE 8' AWAY FROM 2ND STORY WALL OR EXTEND TO 2' ABOVE UPP3ER ROOF. OK TO SHEET ROCK JOISTS WITH 5/8 FIRE RATED SHEET ROCK IF 1" CLEARANCE CANNOT BE MAINTAINED. 2ND FLOOR INSTALL REFER LINES. REMOVE SCREEN FROM DRYER VENT T -TOP. NO ABOVE CEILING ON THIS JOB |