Permit: T04CM02787

Parcel: 140323170

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T04CM02787

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/12/2004 BUILDING - FINAL Approved IVRS - Inspection :*
11/05/2004 BUILDING - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection. Furnace cabinet has been modified. Provide manufacturers approved repair and documents. Furnace not installed per installation manual, see pages 14 and 24
11/03/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) MISSING T-TOP ON ROOF DRYER
2) MASTER BEDROOM CLOSET GLOBE MUSHROOM WITHIN ? OF COMBUSTIBLES
3) BACK WATER VALVE NOT TO FINISH GRADE
4) FURNACE HAS BEEN ALTERED. PROVIDE MANUFACTURERS REPAIR. SPARK SHIELD MUST BE PROPERLY LOCATED
5) ATTIC ACCESS BLOCKING NEEDS ?
11/01/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) EXTEND GAS LINE AT METER CONNECTION AND PROVIDE GAS TEST AND UFER CLAMP MISSING OR BURIED IN WALL 2) NO ADDRESS ON METER 3) SECONDARY CONDENSATE MISSING 90 DEGREE ELBOW AND SEAL AROUND IT 4) EAVE VENTS SOUTH COVERED WITH BLOWN INSULATION 5) CONDENSOR NOT LEVELED 6) CHECK INSTALL INST. FOR CONDENSOTR CLEARANCES AND PROVIDE MANUFACTURER INSTALL INSTRUCTIONS 7) STOPPED INSPECTION
08/24/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*