Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T04CM02787
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/12/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
11/05/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection. Furnace cabinet has been modified. Provide manufacturers approved repair and documents. Furnace not installed per installation manual, see pages 14 and 24 |
|
11/03/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) MISSING T-TOP ON ROOF DRYER 2) MASTER BEDROOM CLOSET GLOBE MUSHROOM WITHIN ? OF COMBUSTIBLES 3) BACK WATER VALVE NOT TO FINISH GRADE 4) FURNACE HAS BEEN ALTERED. PROVIDE MANUFACTURERS REPAIR. SPARK SHIELD MUST BE PROPERLY LOCATED 5) ATTIC ACCESS BLOCKING NEEDS ? |
|
11/01/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) EXTEND GAS LINE AT METER CONNECTION AND PROVIDE GAS TEST AND UFER CLAMP MISSING OR BURIED IN WALL 2) NO ADDRESS ON METER 3) SECONDARY CONDENSATE MISSING 90 DEGREE ELBOW AND SEAL AROUND IT 4) EAVE VENTS SOUTH COVERED WITH BLOWN INSULATION 5) CONDENSOR NOT LEVELED 6) CHECK INSTALL INST. FOR CONDENSOTR CLEARANCES AND PROVIDE MANUFACTURER INSTALL INSTRUCTIONS 7) STOPPED INSPECTION |
|
08/24/2004 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* |