Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 11/09/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection. Front cover of fau modified. Provide 30" of work space infront of FAU. Armaflex laying on b-vent. Platform needs reinforcing |
|
| 11/05/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection. 4" clearance required between weep screen and soil/rock. No ladder access to attic. Stopped inspection |
|
| 11/04/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 4" CLEARANCE REQUIRED BETWEEN WEEP SCREED AND SOIL 2) WATER HEATER SINGLE WALL TO "B" VENT REQUIRES 3 SCREWS 3) FURNACE NOT PROPERLY INSTALLED, SEE INSTALLATION MANUAL 4) CAT WALK NARROW AND BLOCKED BY DUCTWORK BY FAU |
|
| 11/01/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) FAU B VENT MISSING COLLAR 2) FASCIA VENT PLUGGED 3) POST TENSION TAG MISSING 4) BOND CLAMP MISSING 5) SECURE DISCONNECT FLEX TO WALL WITHIN 12" OF DISCONNECT 6) STOPPED INSPECTION |