Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04CM02741

Parcel: 138242920


Addresses:

1944 W BELLAGIO DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
08/18/2004 FRAMING Approved IVRS - Inspection :*
08/17/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) STUCCO LATH NOT NAILED TOP PLATES AT 6" ON CENTER 2) FLASHING MUST BE BEHIND WEEP SCREED AT ENTRY 3) ANCHOR BOLT NUT MISSING AT HOLDOWN 4) ANCHOR BOLTS LOOSE MINIMUM TORQUE 25' LBS 5) M. BATH PLUMBING NOT IN WALL 6) NAIL PROTECT PLUMBING
08/12/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) STUCCO WEEP SCREED MUST EXTEND BELOW SOLE PLATE 2) STUCCO WEEP SCREED MUST HAVE 2" CLEARANCE TO CONCRETE 3) STAPLE LATH AT TOP AND BOTTOM PLATES AT 6" ON CENTER 4) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACES 5) NO DWV WATER TEST 6) TRUSS REPAIR DISCONNECT MUST BE APPROVED BY CITY OF TUCSON 7) TRUSS REPAIR NOT PER REPAIR DOCUMENT 8) HOLDOWN NUTS LOOSE 9) M/BATH PLUMBING OUT OF WALL
08/05/2004 FRAMING Denied IVRS - Inspection :
1) STUCCO ??? MUST OVERLAP STONE WALL SLAB BY A ?? OF 1 1/2. 2). STUCCO WECP ?? MUST BE A MINIMUM OF 2" ABOVE CONCRETE WALKS + SLABS 3) PROVIDE CITY OF TUCSON APPROVED DETAIL FOR WHEEL CHAIR ACCESS WALKWAYS 4) LATH NOT STAPLED AT TOP PLATES AND BOTTOM PLATES 5) ?? NOT INSTALLED 6) CAULK ALL ?? BARRIER ??? 7) WHEEP ?? NOT NAILED TO SILL PLATES 8) 1" CLEARANCE REQUIRED BETWEEN W/H ??? 9) NAIL PROTECT ???OF STUD??? 10) NO D.W.V WATER TEST 11) NO POTABLE WATER TEST. DENIED 12) HOLES CUT IN TRUSS AT ?? PROVIDE TRUSS REPAIR DOCUMENT 13) HOLD DOWN NUTS ?? 14) ?BATH PLUMBING OUT OF WALL
08/04/2004 FRAMING Cancelled IVRS - Ri canceled