Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 09/22/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PAINT A.B.'S PLASTIC VENTS ON ROOF WITH LATEX PAINT 2) OUTSIDE ELECTRIC OUTLETS MUST BE GFCI PROTECTED 3) A/C DISCONNECT ACCESS OBSTRUCTED BY CONDENSER, MUST HAVE 30" X 30" UNOBSTRUCTED WORK AREA 4) MAXIMUM ALLOWED FUSE IN A/C 40 AMP, 45 AMP INSTALLED 5) A/C FLEX CONDUIT LOOSE IN MOUNTING NUTS 6) OUTSIDE HOSE BIBS REQUIRE ANTI-SIPHON VALVES 7) KITCHEN COUNTERS WIDER THAN 12" MUST HAVE GFCI OUTLETS-NOT BEHIND RANGE 8) RANGE OUTLET MUST BE 4 PRONG DEVICE 9) NO POWER TO KITCHEN FLOOR CONVENIENCE OUTLETS 10) CAULK TOILET AND TUB FLOOR 11) CLOSET LIGHT MUST BE 12" IN FRONT OF SHELF 12) DRYER OUTLET MUST BE 4 PRONG OUTLET 13) CAULK FURNACE TO PLATFORM 14) ATTIC ACCESS MUST 22" X 30" 15) HOUSE NOT COMPLETE |