Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2005 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) CHECKED FRAMED OPENING FOR ACCESS PANEL 2) WILL CHECK FRAME AND DOOR ON FINAL |
|
| 06/30/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FRAMED OPENING FOR ACCESS PANEL IN LID-IS NOT IN ALIGNMENT WITH ACCESS IN DUCT WORK 2) THIS NEEDS TO BE LOCATED SO ACCESS TO FIRE DAMPER IN DUCT IS POSSIBLE 3) THE CURTAIN IN THE FIRE DAMPER MUST BE CLOSED AND A NEW LINK INSERTED IF NECESSARY 4) THIS CANNOT BE ACCOMPLISHED IF ACCESS PANELS ARE STAGGERED FO FAR APPART |
|
| 06/16/2005 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |