Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/19/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) INSULATION OK 2) CLOSET FLANGES OK 3) SEE WATER HEATER DETAIL AND SUPPORT WATER HEATER PER PLAN |
|
| 07/11/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) INSULATION IS NOT INSTALLED PER THE SPECIFICATION SEE NOTE NUMBER 4 FROM 6/15/05- READ THE SPECIFICATION AND INSTALL ACCORDINGLY. | |
| 06/30/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*1) WHO LOOKED AT TRAP PRIMERS? SEE NOTE #1 FROM 3/2/05 2) RED LINES ON SITE. OK TO INSULATE. 3) RECALL 3035 AFTER INSULATING HOT PIPES | |
| 06/23/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) NOT INSTALLED PER PLAN. NO REDLINES ON SITE. NO PROVISION FOR INSULATION. | |
| 06/15/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) WATER TEST WASTE AND VENT THRU ROOF OK 2) INSTALL H20 PIPING PER DETAIL (4) OF PAGE 15.3 3) INSTALL FLOOR DRAIN IN NORTH RESTROOM 4) MAKE ACCOMADATIONS FOR INSULATION ON PIPING PER SPEC SECTION 15250-4 |