Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T04CM02692
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/04/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
03/28/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* SUPPORT PIPIG AT BRANCH LINES AT RISER BELOW ROOF. PROVIDE A PRESSURE GAUGE WITH 1/10 PSI INCREMENTATINO THAT HAS A PRESSURE RANGE OF NOT MORE THAN TWICE THE PRESSURE APPLIED. IT IS NOT POSSIBLE TO ENSURE LINE TIGHTNESS IN A REASONABLE AMOUNT OF TIME WITH A 60 PSI GAUGE. |