Permit: T04CM02692

Parcel: 129132110


Addresses:

1110 E 33RD ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM02692

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/11/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/24/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
05/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE LETTER FROM ARCH. ADDRESSING U.G PULL BOX SPLICES, RATING, TYPE, THIS IS A WET LOCATION.
2. SUPPORT 2 1/2" CONDUIT AT EXIST. BLD. PER CODE DO NOT USE EXISTING CONDUIT TO SUPPORT NEW CONDUIT. GROUND 24X24 J-BOX