Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T04CM02692
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/11/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
12/12/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :*OK PVC U.G CONDUITS, NEED TO SEE PLULL BOX INSTALLATION. | |
12/08/2005 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONDUITS NOT TO EXCEED 360 DEG. IN BENDS BETWEEN PULL POINTS - PER NEC |
|
10/06/2005 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*CHECK CONDUIT DEPTH ON EAST END OF TRENCH, SEE NOTES LAST INSP, OK EAST END OF TRENCH. |
|
09/29/2005 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*CONDUIT MUST BE MIN 18" BELOW FINISHED GRADE. CALLED FIRST PER REQUEST LEFT MSG |
|
08/12/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK UNDER WALK WAY WEST OF BLDG |
|
03/11/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK IN SLAB BRANCH CIRCUIT & PANEL FEEDERS/DATA/COMM. |