Permit: T04CM02683

Parcel: 11714091A


Addresses:

420 S 6TH AV


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T04CM02683

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/01/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
UNIT 303 IS THE ONLY UNIT WITH A DISHWASHER.
ALL OTHER UNITS DO NOT HAVE DW INSTALLED AT THIS TIME
DISPOSER BOSSES HAVE BEEN PLUGGED.
05/24/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
05/23/2006 PLUMBING - FINAL Not ready for Inspection CALL INTERMEDIATE TO CLOSE.
SECURE EXP. TANK, SEPARATE COPPER FROM METAL
CAP DISPOSER
DIVERTER VALVES
05/23/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
CUT DOWN EXTERIOR C/O ON EAST END, AND MAKE WATER AND GAS TIGHT W/PIPE THREAD SEALANT.
LABEL ELECTRICAL PANELS "NON METALLIC WATER PIPING"
UNIT 203 TRAP ARMS EXCEEDING 90 DEGREES REQUIRES A CLEAN OUT.
UNIT 303 TRAP ARMS EXCEEDING 90 DEGREES REQUIRES A CLEAN OUT.
DW DRAIN HOSE
DO A BETTER JOB SUPPORTING EXP. TANK
TUB SPOUT