Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T04CM02683
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/01/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* UNIT 303 IS THE ONLY UNIT WITH A DISHWASHER. ALL OTHER UNITS DO NOT HAVE DW INSTALLED AT THIS TIME DISPOSER BOSSES HAVE BEEN PLUGGED. |
|
05/24/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
05/23/2006 | PLUMBING - FINAL | Not ready for Inspection | CALL INTERMEDIATE TO CLOSE. SECURE EXP. TANK, SEPARATE COPPER FROM METAL CAP DISPOSER DIVERTER VALVES |
|
05/23/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* CUT DOWN EXTERIOR C/O ON EAST END, AND MAKE WATER AND GAS TIGHT W/PIPE THREAD SEALANT. LABEL ELECTRICAL PANELS "NON METALLIC WATER PIPING" UNIT 203 TRAP ARMS EXCEEDING 90 DEGREES REQUIRES A CLEAN OUT. UNIT 303 TRAP ARMS EXCEEDING 90 DEGREES REQUIRES A CLEAN OUT. DW DRAIN HOSE DO A BETTER JOB SUPPORTING EXP. TANK TUB SPOUT |