Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2006 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* LEAK CORRECTED AT 1 1/2 SERVICE |
|
| 02/21/2006 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* YARD WATER OK TO COVER ALL EXCEPT FOR LEAKING FITTING AT 1 1/2 SERVICE. PROVIDE BACKFLOW CERTIFICATIONS. |
|
| 02/15/2006 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :*1 1/2'' PVC # 1120 SAYS DWV ON PIPE. PROVIDE A LISTING ALLOWING THIS PIPE FOR PRESSURE APPLICATIONS IF LISTING IS PROVIDED THEN PIPING WILL BE ACCEPTED |
|
| 02/14/2006 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 2101, 2103, 2104 100 PSI TEST ON WATER PIPING OK PIPING NOT YET SECURED OR INSULATED PROTECT PIPING FROM CONCRETE WALLS AND METAL JOISTS |