Permit: T04CM02683

Parcel: 11714091A


Addresses:

420 S 6TH AV


Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T04CM02683

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
02/28/2006 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
LEAK CORRECTED AT 1 1/2 SERVICE
02/21/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
YARD WATER OK TO COVER ALL EXCEPT FOR LEAKING FITTING AT 1 1/2 SERVICE.
PROVIDE BACKFLOW CERTIFICATIONS.
02/15/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*1 1/2'' PVC # 1120 SAYS DWV ON PIPE.
PROVIDE A LISTING ALLOWING THIS PIPE FOR PRESSURE APPLICATIONS
IF LISTING IS PROVIDED THEN PIPING WILL BE ACCEPTED
02/14/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
2101, 2103, 2104 100 PSI TEST ON WATER PIPING OK
PIPING NOT YET SECURED OR INSULATED
PROTECT PIPING FROM CONCRETE WALLS AND METAL JOISTS