Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T04CM02683
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/24/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/24/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CLOSET FLANGES ALL LEVELS OK |
|
03/03/2006 | PLUMBING - INTERMEDIATE | Partial Approval | 1) LEVEL #2 WAS COVERED PRIOR TO INSPECTING 2) WATER PIPE PROTECTION FROM METAL JOISTS 3) PROVIDE AN ACCESS HOLE IN THE WALL FOR INSPECTION PURPOSES 4) LEVEL 1: WATER PIPING HAS NOT BEEN PROTECTED FROM METAL JOISTS. DO NOT COVER 5) SUPPORT HORIZONTAL ABS VENT AT KITCHENS 6) SUPPORT VENTS IN 2102 7) CORRECT LEAK ON 2202 BELOW FLOOR 8) WATER TEST OK ON 2101, 2102, 2103 AND 2104 |
|
03/02/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 2201 WATER PIPING TEST OK 2) 2201 DWV APPROVED 3) 2102 WATER PIPING TEST OK |
|
02/01/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CORRECTIONS ON BELOW FLOOR HORIZONTAL VENTING FOR UNITS 2301, 2302, 2303 HAVE BEEN MADE 2) DWV OK UNITS 2201, 2202 AND 2203 OK EXCEPT FOR CLEANOUT EXTENSIONS REQUIRED AT LAUNDRY 2202 AND KITCHEN 2202 AND 2203 3) INSULATION ON FIRST 8' AT WH OK 4) PROTECT PEX PIPING FROM METAL JOISTS IN 2201-2203 |
|
01/26/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* #2202 WATER PIPING AND 100 PSI TEST OK - READY FOR INSULATION #2203 WATER PIPING AND 100 PSI TEST OK - READY FOR INSULATION #2204 WATER PIPING AND 100 PSI TEST OK - READY FOR INSULATION |
|
01/17/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UNIT 2301.2302.2303 TEST ON WATER PIPING - OK, ICE MAKER BOX - OK DRAINAGE FITTINGS REQUIRED ON HORIZONTAL VENTS BELOW THE FLOOD RIM OF FIXTURES (BELOW FLOOR) RETEST DWV, CALL FOR INSPECTION OK TO COVER WALLS ON 3RD LEVEL AFTER COMPLETING VENT LINES FROM LOWER LEVELS |
|
01/13/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 2302 - SECURE PIPING AT VALVE GOT WATER PIPING IN WALL AT LAUNDRY BOX LOCATION 2303 - REPLACE BROKEN ICE MAKER BOX SECURE PIPING AT ICE MAKER BOX PROTECT PEX MAIN FROM MASONRY WALLS RETEST AFTER REPLACING BOX |
|
12/27/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2101 PIPE WRAPS OK FOR CONCRETE |