Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM02682
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/02/2008 | MECHANICAL - FINAL | Approved | ||
05/05/2006 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
04/28/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* CLOTHES DRIERS, VENTED UP THROUGH ROOF TERMINATIONS AND BASEMENT INSTALLATIONS TWENTY FIVE <25> TOTAL EXCEED MAXIMUM DEVELOPED LENGTH ALLOWED BY IMC SEC. 504/504.6.1 A G.E MODEL #DIR483EG WILL PROVIDE THE NECESSARY AIR TO MEET SEC. 504.6.1 |
|
04/26/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. VERIFY THAT 180 DEG. ROOFTOP BEND IS INCLUDED IN DUCT LENGTH (+10') 2. VERIFY BACKDRAFT DAMPERS ARE NOT REQUIRED FOR ROOFTOP TERMINATION OF DRYERS. 3. 1/4" MESH REQUIRED AT ATTIC TERMINATION OF BOTH EXHAUST. 4. I DID NOT VERIFY HUMIDISTAT CONTROL OF ATTIC BLOWER |
|
03/31/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* SEE SEC. 504.6 504.6.1 IMC DOMESTIC DRYER VENT LENGTH. |