Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T04CM02682
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/02/2008 | MECHANICAL - INTERMEDIATE | Approved | ||
03/30/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* HALLWAY #1111 - 4" DRYER VENT IN WALL 1. TERMINATING NORTH WALL FROM BASEMENT 2. OWNER/ENGINEER NEED TO START PRODUCING PAPER WORK ON DRYER EQUIP. THAT MEETS THE DISCHARGE LENGTH FOR APPROVAL. THIS ISSUE WAS DISCUSSED ON 10/04/05 |
|
03/23/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ATTIC REJECTED CONDENSATE PIPING OK DO NOT RECALL UNTIL FINISHED ELECTRICIAN, MEANS OF DISCONNECT IN ATTIC?? PICK UP WIRE FROM WALKWAY. |
|
03/12/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. BALANCE OF FAN COILS IN BASEMENT 2. CONDENSATE PIPING OK I.D. W/NUMBERS FAN COILS/MATCHING COND. |
|
03/05/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/28/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER FULL OPENING FRAMED IN. OK TO COVER. |
|
01/27/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*# 1206 CLEAR FULL FRONT, ACCESS TO FAN COIL | |
01/17/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
11/30/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*DISCUSSED SUSPENDED CASED FAN COILS. CONDENSATE RUN OFFS, PIPING & ELECT. CONNECTIONS | |
11/28/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*APPLIANCES IN ATTIC. 306.3 ELECT. REQUIREMENTS 306.3.1 A LIGHT FIXTURE IS NECESSARY TO SERVICE FAN COILS IN THESE CONCEALED SPACES |
|
11/23/2005 | MECHANICAL - INTERMEDIATE | Cancelled | CANCELLED PER J MILITELLO ON 11/23/05-SHORT STAFFED | |
11/07/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*APPROVED DRAWING DRYER VENT. ALL SECUR. WIRING ,?? ETC. REMOVE FROM FAN COIL ACCESS. 2ND FLR OK TO COVER |
|
11/04/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*DO NOT BLOCK ATIC ACCESS OPENINGS. RELOCATE ACCESS IN ROOM 1304 SEAL ALL JOINTS & CONNECTIONS ON EXHAUST DUCTS. PROVIDE PLATE STRAPS WHERE NEEDED SUPPORT PVC DRAIN LINES EVERY 4' |
|
10/04/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*DISCUSSED DRYER DUCTS. TOTAL LENGHTS SUPPLY DUCTS, INSULATE ALL SUPPLY FLARED REGISTER BOXES AS NECESSARY ON ALL FLOORS. |