Permit: T04CM02682

Parcel: 11714096A


Addresses:

460 S 6TH AV


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T04CM02682

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/16/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*2" PEX MAIN RISERS FROM BASEMENT LEVEL THROUGH 2ND AND 3RD LEVELS AND MAINS ON 2ND & 3RD LEVELS OK TO COVER 100 PSI TEST OK
01/19/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WASTE PIPING FOR UNIT 1206 - OK
CONTINUATION OF 4" VENT IN UNIT 1306 - 4" TO 6" OK
CONTINUATION OF 4" VENT IN UNIT 1309 - OK
01/17/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
UNIT 1206 PIPING IN WALLS OK TO COVER, BUT DRAIN PIPING BELOW FLOOR HAS TO MANY CHANGES OF DIRECTIONS WITHOUT CLEANOUTS
COMPLETE T&P AND WH PAN DRAINS
01/13/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1206 LEAK ON VENT - SAFETY PLATES MISSING AT KIT. SINK
01/11/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 1206 100 PSI PRESSURE TEST-OK
2) PIPING NOT SECURED
3) SEPERATE HOT AND COLD, SECURE, INSULATE-RECALL FOR INSPECTION
4) 1106 100 PSI TEST-OK
5) SECURE ICE MAKER BOX, SECURE SOV SEPERATE HOT AND COLD
6) 1105 100 PSI TEST OK PEX SHALL BE SUPPORTED AT 32"
7) 1107 100 PSI TEST-OK PEX SHALL BE SUPPORTED AT 32"
8) 1108 100 PSI TEST-OK PEX SHALL BE SUPPORTED AT 32"
12/23/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*RM 2102 ( UNDER SEPARATE PERMIT) WRAPPED AND READY FOR CONCRETE.
UNITS 1101,1102,1103 & 1104 ABS OK
INSULATION OK
NEED TO SEE CLOSET FLANGES
CONDENSATE WASTE MAY NOT TERMINATE AT WASHER BOX STAND PIPE
OK TO COVER WALLS.
12/21/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/20/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DETAIL LISTING ON CONTINUATION SHEET: 1103, ROOM 1102-CORRECT DRIP ON SOVS, ROOM 1101-SUPPORT SOVS, ROOM 1104-SUPPORT DIVERTERS
2) WATER PIPING, 100 PSI TEST-OK
3) OK TO INSULATE
12/14/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RM. #1306 PIPING IN WALLS OK TO COVER, EXCEPT THAT VENTING REQUIREMENTS IN BATHROOM AREA WHERE 2" IS INCREASED TO 6" HAVE NOT BEEN RESOLVED.
12/13/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER TEST OK FOR CHAPEL
#1306
INSULATE WATER AND PROTECT FROM DAMAGE
12/09/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
RM 1306 CHAPPLE
PROVIDE 50 PSI TEST ON WATER PIPING INSULATE WHERE NECESSARY
PROVIDE 2% SLOPE ON KIT WASTE
INCREASE 2" TO 6" VENT - DOES NOT MEET CROSS SECTIONAL AREA VENTING REQUIREMENTS.
12/07/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) INSULATION ON 8' OF COLD WATER PIPING AT WHS OK, ALL ROOMS EXCEPT 1306 AND 1206
11/28/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*INSULATION OF HOT AND COLD WATER PIPING TO 8' BACK FROM WATER HEATER IN ROOMS
1201-1204, 1301-1304, 1307-1310
11/23/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/21/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*3RD FLOOR WATER PIPING INSULATED W/ 12 ARMORE FLEX ON 8' OF HOT ONLY PIPING FROM WATER HEATER.
PROVIDE INSULATION ON 8' OF COLD WATER PIPING TO WATER HEATER.
11/16/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/14/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WATER TEST OK ALL 4 UNITS WASTE AND WATER PIPING
2) PROVIDE SUPPORT ON PEX ABOVE CEILING
3) PROVIDE INSULATION ON WATER PIPING
4) PROVIDE CLEARANCE OR INSULATION FOR PEX ON ? WATER
WHERE TOUCHING DRYER VENT
UNITS 1201, 1202,1203
WATER & WASTE TEST OK
SECURE ?? ON WATER SUPPLY
CLOSET FLANGES MUST BE SECURED W/BRASS SCREWS CALL FOR CLOSET FLANGE INSPECTION
11/07/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) MODEL ENERGY CODE REQUIRES INSULATION ON HOT WATER
2) 3RD FLOOR ABS OK TO TEN FEET ABOVE CEILING
3) 3RD FLOOR PEX OK TO INSULATE
4) CONTRACTOR TO ADD HANGERS ABOVE 2ND FLOOR AS REQUIRED