Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T04CM02682
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/16/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :*2" PEX MAIN RISERS FROM BASEMENT LEVEL THROUGH 2ND AND 3RD LEVELS AND MAINS ON 2ND & 3RD LEVELS OK TO COVER 100 PSI TEST OK | |
01/19/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WASTE PIPING FOR UNIT 1206 - OK CONTINUATION OF 4" VENT IN UNIT 1306 - 4" TO 6" OK CONTINUATION OF 4" VENT IN UNIT 1309 - OK |
|
01/17/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UNIT 1206 PIPING IN WALLS OK TO COVER, BUT DRAIN PIPING BELOW FLOOR HAS TO MANY CHANGES OF DIRECTIONS WITHOUT CLEANOUTS COMPLETE T&P AND WH PAN DRAINS |
|
01/13/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1206 LEAK ON VENT - SAFETY PLATES MISSING AT KIT. SINK |
|
01/11/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 1206 100 PSI PRESSURE TEST-OK 2) PIPING NOT SECURED 3) SEPERATE HOT AND COLD, SECURE, INSULATE-RECALL FOR INSPECTION 4) 1106 100 PSI TEST-OK 5) SECURE ICE MAKER BOX, SECURE SOV SEPERATE HOT AND COLD 6) 1105 100 PSI TEST OK PEX SHALL BE SUPPORTED AT 32" 7) 1107 100 PSI TEST-OK PEX SHALL BE SUPPORTED AT 32" 8) 1108 100 PSI TEST-OK PEX SHALL BE SUPPORTED AT 32" |
|
12/23/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*RM 2102 ( UNDER SEPARATE PERMIT) WRAPPED AND READY FOR CONCRETE. UNITS 1101,1102,1103 & 1104 ABS OK INSULATION OK NEED TO SEE CLOSET FLANGES CONDENSATE WASTE MAY NOT TERMINATE AT WASHER BOX STAND PIPE OK TO COVER WALLS. |
|
12/21/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
12/20/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DETAIL LISTING ON CONTINUATION SHEET: 1103, ROOM 1102-CORRECT DRIP ON SOVS, ROOM 1101-SUPPORT SOVS, ROOM 1104-SUPPORT DIVERTERS 2) WATER PIPING, 100 PSI TEST-OK 3) OK TO INSULATE |
|
12/14/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RM. #1306 PIPING IN WALLS OK TO COVER, EXCEPT THAT VENTING REQUIREMENTS IN BATHROOM AREA WHERE 2" IS INCREASED TO 6" HAVE NOT BEEN RESOLVED. |
|
12/13/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER TEST OK FOR CHAPEL #1306 INSULATE WATER AND PROTECT FROM DAMAGE |
|
12/09/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* RM 1306 CHAPPLE PROVIDE 50 PSI TEST ON WATER PIPING INSULATE WHERE NECESSARY PROVIDE 2% SLOPE ON KIT WASTE INCREASE 2" TO 6" VENT - DOES NOT MEET CROSS SECTIONAL AREA VENTING REQUIREMENTS. |
|
12/07/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) INSULATION ON 8' OF COLD WATER PIPING AT WHS OK, ALL ROOMS EXCEPT 1306 AND 1206 |
|
11/28/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*INSULATION OF HOT AND COLD WATER PIPING TO 8' BACK FROM WATER HEATER IN ROOMS 1201-1204, 1301-1304, 1307-1310 |
|
11/23/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
11/21/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*3RD FLOOR WATER PIPING INSULATED W/ 12 ARMORE FLEX ON 8' OF HOT ONLY PIPING FROM WATER HEATER. PROVIDE INSULATION ON 8' OF COLD WATER PIPING TO WATER HEATER. |
|
11/16/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
11/14/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) WATER TEST OK ALL 4 UNITS WASTE AND WATER PIPING 2) PROVIDE SUPPORT ON PEX ABOVE CEILING 3) PROVIDE INSULATION ON WATER PIPING 4) PROVIDE CLEARANCE OR INSULATION FOR PEX ON ? WATER WHERE TOUCHING DRYER VENT UNITS 1201, 1202,1203 WATER & WASTE TEST OK SECURE ?? ON WATER SUPPLY CLOSET FLANGES MUST BE SECURED W/BRASS SCREWS CALL FOR CLOSET FLANGE INSPECTION |
|
11/07/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) MODEL ENERGY CODE REQUIRES INSULATION ON HOT WATER 2) 3RD FLOOR ABS OK TO TEN FEET ABOVE CEILING 3) 3RD FLOOR PEX OK TO INSULATE 4) CONTRACTOR TO ADD HANGERS ABOVE 2ND FLOOR AS REQUIRED |