Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T04CM02682
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/02/2008 | PLUMBING - ROUGH, SOIL | Approved | ||
01/23/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
12/02/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
10/20/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) 4" BLDG DRAIN EXISTS BLDG AT SOUTH WEST CORNER WILL NEED TO SEE TEST TO EJECTOR AT LATER DATE |
|
10/17/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*ADDITION OF 2" WASTE FOR LAUNDRY BOX PER DELTA 4 DATED 7/19/05 PER KEN CAWTHORNE SEALLED PLAN ( SMU MECH) WATER TEST OK WILL NEED CITY APPROVED REVISED PLAN OF THIS. PIPE WRAPS OK ON ALL UNITS. | |
09/16/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 4" BUILDING DRAIN FROM 8' FROM SOUTH WEST CORNER OF INTERIOR OF BUILDING THRU (8) UNITS TO END OF CLINE FLOOR CLEANOUT WATER TEST TO BELOW REVENT LIOIGHT? OK 1) NEED TO VIEW PIPE WRAPS PRIOR TO CONCRETE 2) WATER HEATERS WILL REQUIRE CORRECT T AND P DRAIN REQUIREMENTS AND ACCESS PER 94 UPC |