Permit: T04CM02682

Parcel: 11714096A


Addresses:

460 S 6TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T04CM02682

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
03/23/2006 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
03/13/2006 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
CANCEL PER LUIS (JRM ELECTRIC)
02/23/2006 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
OK TO CLEAR CEC (CABLE DROP OK TO METER)
1001, 1002, 1003, 1004, 1005, 1006, 1007, 1008, 1101, 1102, 1103, 1104, 1105, 1106, 1107, 1108, 1201, 1202, 1203, 1204, 1205, 1206, 1207, 1208, 1209
1. COMPLETE INSTALL EM. LIGHTING, EXITS, LIGHT FIXTURES IN UNITS.
2. NEED PLAN REVISIONS FOR SERVICE AND UNIT PANEL MODIFICATIONS, FEEDER SIZES, TYPES COPPER/ALUM. HOUSE PANEL MOD.
3. INSTALL PANEL SCHEDULE
4. SUPPORT CABLING IN ATTIC
5. COMPLETE EM. LIGHTING, EXITS GROUND FLOOR
6. OK GROUNDING AT SERVICE.