Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2006 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
| 03/13/2006 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* CANCEL PER LUIS (JRM ELECTRIC) |
|
| 02/23/2006 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* OK TO CLEAR CEC (CABLE DROP OK TO METER) 1001, 1002, 1003, 1004, 1005, 1006, 1007, 1008, 1101, 1102, 1103, 1104, 1105, 1106, 1107, 1108, 1201, 1202, 1203, 1204, 1205, 1206, 1207, 1208, 1209 1. COMPLETE INSTALL EM. LIGHTING, EXITS, LIGHT FIXTURES IN UNITS. 2. NEED PLAN REVISIONS FOR SERVICE AND UNIT PANEL MODIFICATIONS, FEEDER SIZES, TYPES COPPER/ALUM. HOUSE PANEL MOD. 3. INSTALL PANEL SCHEDULE 4. SUPPORT CABLING IN ATTIC 5. COMPLETE EM. LIGHTING, EXITS GROUND FLOOR 6. OK GROUNDING AT SERVICE. |