Permit: T04CM02662

Parcel: 103080110

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM02662

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
09/29/2005 FRAMING Approved IVRS - Inspection :*
03/24/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BLOCKING REPAIR INADEQUATE AT HOLE
2) CUT IN SHEARWALL HAVE ENGINEER OF RECORD
3) SUPPLY DETAIL AND COMPLY
4) HEARTH FIREPLACE INCOMPLETE
03/21/2005 FRAMING Partial Approval IVRS - Inspection :*
1) FIREPLACE SPECS CALL FOR 16" NON COMBUSTIBLE HEARTH
2) BLOCK AROUND ELECTRIC CUT OUT GARAGE SHEARWALL (EXCESSIVE HOLE CUT)
3) OK TO INSULATE AND ROCK. LEAVE AREAS OF CONCERN OPEN AND RECALL ( COULD NOT LOCATE PREVIOUS INSPECTION PAPERWORK)
03/18/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO TEST POTABLE H20 SYSTEM
2) NEED ACCESS TO JACUZZI TUB EQUIPMENT
3) BLOCK ECESSIVELY CUT HOLE SHEARWALL #5 GARAGE
4) GAS TEST MINIMUM 10 POUND REQUIRED
03/14/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) NEED ?? JOIST SPECS FROM MANUF. PROVIDE ACCESS JACUZZI ELECTRIC EQUIP. 2) WHAT IS ELECT BOX FOR IN BATH CLOSET AREA AT FLOOR NORTH SIDE 3) INSTALL A 35/H25 INTERIOR LEDGES TO STUDS. 4) INSTALL COMB/RELIEF VENTS MECH ROOM-CEILING HEIGHT TO HIGH TO ALLOW ??VENTS. 5) APPEARS SKYLIGHT TO HAVE DBL. JOISTS BOTHSIDES. 6) SUPPORT DROPPED CEILING FRONT ENTRY MORE SECURELY & KITCHEN AREA. 7) NO TEST POTABLE WATER 8) BLOCK ALL SIDES EXCESSIVELY CUT HOLE ?? # 5 S.W. 9) ELECTRIC CAN LIGHT HANGING LOOSE 10) STOPPED INSPECTION.