Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM02648
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/28/2005 | FRAMING | Approved | IVRS - Inspection :*AP | |
01/18/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HOLDOWN BOLTS NOT INSTALLED 2) CHANNEL NOT NAILED PER 10/SD4 3) DRAG TRUSS NOT NAILED PER 6A/SD3 4) SHEARWALL G-1 DBL TOP PLATE CUT FOR RANGE HOOD. PROVIDE ENGINEERS APPROVED REPAIR DETAIL 5) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE (4 PLACES) 6) OSB SHEAR NOT NAILED PER PLAN |