Permit: T04CM02648

Parcel: 136406260

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/28/2005 FRAMING Approved IVRS - Inspection :*AP
01/18/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HOLDOWN BOLTS NOT INSTALLED
2) CHANNEL NOT NAILED PER 10/SD4
3) DRAG TRUSS NOT NAILED PER 6A/SD3
4) SHEARWALL G-1 DBL TOP PLATE CUT FOR RANGE HOOD. PROVIDE ENGINEERS APPROVED REPAIR DETAIL
5) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE (4 PLACES)
6) OSB SHEAR NOT NAILED PER PLAN