Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T04CM02610

Parcel: 133231910

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/15/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK FINAL
12/13/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :OK TEMP C/O
11/30/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) LOOKED AT PAPERWORK
11/18/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/GENERATOR HAS BEEN TESTED - PAPER WORK ENCLOSED 1)INSTALL SIGN CABELS AS PER 700.8 2)FINISH ITEMS #3 PREVIOUS INSPECTION
11/15/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) EXTENDER RINGS NOT TO BE METAL-ALSO OUTSIDE WALL LIGHTS AND CANS
2) IDENTIFY EMERGENCY CIRCUITS AT WALL PLATES 3) VERIFY LISTING AND LABELING FOR ? MANIFOLD EQUIPMENT, VACCUM PUMP SYSTEM
4) COLOR CODE CONDUCTORS
5) OK TEMP C OF O FOR BRINGING IN MEDICAL EQUIPMENT TESTING
11/10/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*