Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
| 12/13/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :OK TEMP C/O | |
| 11/30/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ 1) LOOKED AT PAPERWORK | |
| 11/18/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/GENERATOR HAS BEEN TESTED - PAPER WORK ENCLOSED 1)INSTALL SIGN CABELS AS PER 700.8 2)FINISH ITEMS #3 PREVIOUS INSPECTION | |
| 11/15/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ 1) EXTENDER RINGS NOT TO BE METAL-ALSO OUTSIDE WALL LIGHTS AND CANS 2) IDENTIFY EMERGENCY CIRCUITS AT WALL PLATES 3) VERIFY LISTING AND LABELING FOR ? MANIFOLD EQUIPMENT, VACCUM PUMP SYSTEM 4) COLOR CODE CONDUCTORS 5) OK TEMP C OF O FOR BRINGING IN MEDICAL EQUIPMENT TESTING |
|
| 11/10/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |