Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM02610
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/10/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) OPERATION ROOM JUNCTION BOX ACCESS AND RELOCATE OK 2) PANEL BOARDS EC-1, EC-2, P-1 AND P-2 APPROVED |
|
| 11/03/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) OK TO TILE | |
| 11/01/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) RECEIVED LETTER FOR TORQUE 2) LEAVE OPEN AT CABLE TRAY UNTIL COMPLETE 3) FINISH SUPPORT WIRES TO FIXTURES 4) JUNCTION BOXES ABOVE HARD CEILING TO BE ACCESSIBLE | |
| 10/29/2004 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 10/18/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |