Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM02610
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/13/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
11/10/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) OPERATION ROOM JUNCTION BOX ACCESS AND RELOCATE OK 2) PANEL BOARDS EC-1, EC-2, P-1 AND P-2 APPROVED |
|
11/03/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) OK TO TILE | |
11/01/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) RECEIVED LETTER FOR TORQUE 2) LEAVE OPEN AT CABLE TRAY UNTIL COMPLETE 3) FINISH SUPPORT WIRES TO FIXTURES 4) JUNCTION BOXES ABOVE HARD CEILING TO BE ACCESSIBLE | |
10/29/2004 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
10/18/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |