Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM02598
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/21/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
07/15/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*PARTIAL APPROVAL. OK TO TILE EXCEPT AS NOTED. FINISH ITEMS #3, 4, 5 OF PREVIOUS INSPECTION. | |
07/14/2004 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :*/ 1) 4 SCREWS PER FIXTURE IF CORNERS ARE USED-2 IF CENTER 2) EXTENDER RING MAY BE NEEDED FOR LIGHTS IN TILES 3) WIRES TO BE INDEPENDENTLY SUPPORTED 300.11 NOT ON CEILING WIRES 4) VDV CABLES NOT TO LAY ON GRID-SUPPORT WITH APPROVED METHODS 5) SUPPORT CONDUIT WITHIN 3' OF BOXES 6) LIGHT FIXTURE HAS COPPER LINE SO AS FIXTURE CANNOT BE MOVED 7) FINISH BOX MAKE UP AND BOXES TO BE ACCESSIBLE |