Permit: T04CM02597

Parcel: 11812051A


Addresses:

234 E 22ND ST #1M

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/20/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/03/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* OK TO CLEAR SERVICE 2M ECO NO BOND REQUIRED FIRE REPAIR CALL FOR FINAL AFTER EQUIP SHOWN ON E-2 OF PLAN CONNECTED
01/31/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* NOTES. THERES IS TWO SERVICES AT THIS ADDRESS, PLEASE CLARIFY ADDRESSES FOR EACH SERVICE THRU PIMA COUNTY ADDRESSING, SERVICE TO BE ENERGIZED MUST HAVE DESIGNATED ADDRESS LABEL & MUST BE ASSIGNED TO THIS PERMIT.
01/27/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* NOTES: 1) GROUNDING ELECTRODE CONDUCTOR MUST BE CONTINUOUS, UNSPLICED AS SPECIFIED IN 250-64 NEC AT SERVICE.
01/21/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* NOT READY SEE LAST INSP. WRITE-UP
01/20/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* 1) INSTALL GROUNDING ELECTRODE SYSTEM AT SERVICE,PER 250 NEC. 2) INSTALL FUSES & R-PINS IN SERVICE DISCONNECT SWITCHES AND LABEL DISCONNECTS. 3) BOND BUSHINGS OR BOND LOCKNUTS REQUIRED BOTH SIDE OF NIPPLES BETWEEN GUTTER & DISCONNECT SWITCHES. PER 250-94 NEC