Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/20/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/03/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TO CLEAR SERVICE 2M ECO NO BOND REQUIRED FIRE REPAIR CALL FOR FINAL AFTER EQUIP SHOWN ON E-2 OF PLAN CONNECTED | |
| 01/31/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* NOTES. THERES IS TWO SERVICES AT THIS ADDRESS, PLEASE CLARIFY ADDRESSES FOR EACH SERVICE THRU PIMA COUNTY ADDRESSING, SERVICE TO BE ENERGIZED MUST HAVE DESIGNATED ADDRESS LABEL & MUST BE ASSIGNED TO THIS PERMIT. | |
| 01/27/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES: 1) GROUNDING ELECTRODE CONDUCTOR MUST BE CONTINUOUS, UNSPLICED AS SPECIFIED IN 250-64 NEC AT SERVICE. |
|
| 01/21/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NOT READY SEE LAST INSP. WRITE-UP | |
| 01/20/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTALL GROUNDING ELECTRODE SYSTEM AT SERVICE,PER 250 NEC. 2) INSTALL FUSES & R-PINS IN SERVICE DISCONNECT SWITCHES AND LABEL DISCONNECTS. 3) BOND BUSHINGS OR BOND LOCKNUTS REQUIRED BOTH SIDE OF NIPPLES BETWEEN GUTTER & DISCONNECT SWITCHES. PER 250-94 NEC |