Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/12/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 07/23/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) SEE 314.16 (B) FOR ALLOWABLE WIRE FILL (HANDY BOXES ARE TOO SMALL FOR THE AMOUNT OF WIRE FILL) 2) REVISE PLAN ON ADDED RECEPTACLES (HAVE AVAILABLE AT FINAL INSPECTION) 3) RACEWAYS APPROVED FOR BURIEL ONLY WHERE CONCRETE ENCASED, SHALL REQUIRE CONCRETE ENVELOP NOT LESS THAN 2" THICK TABLE 300.5 NOTE 2 |