Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2004 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
| 06/15/2004 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) EXPOSE FOOTING AT EAST SIDE TO VERIFY SRE 2) OPEN EAST SIDE WALL TO VERIFY 1 HR. FIRE WALL CONSTRUCTION 3) DOUBLE 2 X 8 BEAM IS NOT ADEQUATE TO SUPPORT ROOF 4) 4 X 6 BEAM IS NOT ADEQUATE TO SUPPORT END OF DOUBLE 2 X 8 BEAM 5) OBTAIN WASTE WATER PERMIT FOR ALL PLUMBING INSTALLED 6) PROVIDE GAS PRESSURE TEST ON GAS LINE 7) GAS VALVE MUST BE ATTACHED TO APPLIANCE OR CAPPED |
|
| 06/14/2004 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* |