Permit: T04CM02547

Parcel: 11415008T


Addresses:

8140 S HOUGHTON RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T04CM02547

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2005 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*CORRECTIONS HAVE BEEN MADE. OK FOR CEILING TILES
10/04/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*DUCTS TO BE SUPPORTED FROM THE STRUCTURE W/1 1/2" WIDE 26 GA STRAPS
09/29/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ALL UNITS STRAP RETURN AIR FLEX UP OFF OF CEILING
2) FINISH INSULATING TAP INS AND SEAL JOINTS
3) WILL CHECK MINI SPLIT ON FINAL
4) HAVE YOUR ENGINEER DESIGN A MEANS TERMINATING CONDENSATE