Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/06/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO INSULATE 2) SECURE ALL WIRES AT BOXES 3) NEED SEPERATE CIRCUIT FOR WINDOW A/C, SIZE WIRE PER UNIT U.L. LABEL 4) DRYER CIRCUIT 3 INSULATED WIRES, CONDUIT OK FOR GRD, 2 BLACK/WHITE 5) NEED MID-WEST BOX FOR COOLER |
|
| 12/30/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |