Permit: T04CM02534

Parcel: 133148180


Addresses:

6555 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
09/24/2004 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*/25 PSI AIR TEST FROM METER LOCATION 2" TO (12) HANGING RADIANT HEATERS OK 1) INSTALL DRIP LEGS AND APPROVED VALVES HAVE HEATERS INSTALLED WITH CORRECT CONNECTION AND RETEST SYSTEM