Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/02/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 09/28/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/OK CONDUIT AT RESTRUANT PATIO, FOUNTAIN. OK PVC IN GROUND AT FOUNTAIN. 1)FILL UNUSED OPENINGS IN BOXES 2) CHASE NIPPLE FOR PASSING THRU PARTITION ONLY NOT AS FITTINGS 3)LIGHTING TO MEET LIGHTING CODES 4)DRIVE CONDUITS COVERED WITHOUT INSPECTION - CONTRACTOR INFORMES ME WE ONLY HAVE 12" UNDER DRIVE - 24" NEEDED PER 300.5 5)BOXES TO BE ABOVE GRADE |