Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM02508
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/02/2004 | FRAMING | Approved | IVRS - Inspection :* | |
09/01/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SAME AS BEFORE |
|
08/31/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
08/30/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) 3" MINIMUM BEARING REQUIRED UNDER BEAM AT CLOSET 2) HAVE ENGINEER OF RECORD APPROVE AS BUILT IN WRITING |
|
08/27/2004 | FRAMING | Not ready for Inspection | IVRS - Inspection :*/ 1) 2-2 X 4 STUDS REQUIRED AT DBL 2 X 10 BEAM AT ENTRY WITH MINIMUM 3" BEARING EACH SIDE 2) BLOCK AROUND COME AND RELIEF GRILLS | |
08/13/2004 | FRAMING | Not ready for Inspection | IVRS - Inspection :*/ 1) COMPLETE STUCCO MESH |